Diagnostics / Service (RS 232C)
This port is intended only for internal system testing. (Output of failure messages when the system
configuration is transferred.)
Reset Terminal (Reset Latching Alarms)
Latching alarms can be released via terminals 7 and 8 by closing a contact (key, etc.) (same func-
tion as the RESET key on the front panel).
Acknowledge Terminal (Reset Horn Relay)
The horn relay can be reset via terminals 5 and 6 by closing a contact (key, etc.) (same function
as the ACKNL key on the front panel).
LOCR Terminal
The relay inhibit for the MRO 8 module (common alarms) on the rear of the rack can be activated
via terminals 3 and 4 by closing a contact (key, etc.). All 8 modules are inhibited as a block. This
terminal has no effect on the MRO 8 TS modules. These modules are inhibited via the LOCK ter-
minal on the MRC TS module (Chapter 10.7).
NOTE: If the voltage supply for the MIB module is interrupted, the inhibiting function of the MRO
8 modules is no longer active.
Password Terminal
The input of the configuration password can be replaced via terminals 1 and 2 by closing a contact
(key switch). If the current password has been forgotten, this terminal can be used to enter a new
password (Chapter 10.5).
MST Terminal 8: RES
MST Terminal 7: GND
MST Terminal 6: HACK
MST Terminal 5: GND
MST Terminal 4: LOCR
MST Terminal 3: GND
MST Terminal 2: PSW
MST Terminal 1: GND