Operation of the System
SUPREMATouch
37
US
Normal [energised]
Field type: Selection
Set the operating mode for the selected relay output:
- Normally energised [“closed circuit”]:
The relay coil is energised in the no alarm status and is de-energised in the alarm status.
- Normally de-energised [“open circuit”]:
The relay coil is de-energised in the no alarm status and is energised in the alarm status.
Tag
Field type: Text
Enter a customer-specific designation for the selected relay output.
blk. [flashing]
Field type: Checkbox
If this field is set, the relay flashes at a frequency of approx. 1 Hz when activated. This function
doesn't work together with the inhibit condition.
New Alarm [i. e. actual alarm]
Field type: Check box
If this field is set, the relay output selected can be set to “normal” status by pressing the <ACKNL>
key even if the signal value has been outside the alarm threshold limits.
OK
Field type: Button
Tapping this button validates the settings entered for the selected relay output. When the button
is tapped, the voting settings must not be higher than the number of conditions set in the check
boxes. If this is the case, they become part of the system’s parameter set. If not, a warning ap-
pears.
Cancel
Field type: Button
Pressing this button discards the settings entered for the selected relay output.
Clear
Field type: Button
Pressing this button deletes all of the parameters for the selected relay output. The output then
returns to the status it was before it was set up the first time.