NIBE FIGHTER 1250
- Factory setting: 25 °C
Menu 9.2.9.4 Numb. of days per. 2 [S]
Selection of the number of days in period 2.
The value can be set between 1 and 5.
- Factory setting: 5
Menu 9.2.9.5 Temp. period 2 [S]
Selection of the fl ow temperature in period 2.
The value is adjustable between 15 and 50 °C
- Factory setting: 40 °C
Menu 9.2.9.6 Return [S]
Pressing the enter button returns you to Menu 9.2.9.0
Menu 9.2.10 Pool control [S]
Select ”On” if POOL11 is installed.
Menu 8.4.0 can be accessed.
Selection option Off and On.
- Factory setting: Off
Menu 9.2.11 Brine pressostat [S]
You set here whether an external brine pressostat/load
monitor is connected to the load monitor card.
Selection option Off and On.
- Factory setting: Off
Menu 9.2.12 Oper. mode brinepump [S]
Operating mode for the brine pump set here.
Selection option :
Intermittent: The brine pump starts 60 seconds before and
stops after the compressor.
Continuous: Continuous operation.
10 days cont: Continuous operation for 10 days at max
speed Then the pump shifts to intermittent
operation.
- Factory setting: Intermittent
Menu 9.2.14 Factory setting [S]
Here you can restore factory settings in FIGHTER 1250.
When returning to the factory settings the language
switches to English.
Selection option Off and On.
- Factory setting: Off
Menu 9.2.15 RCU Present [S]
Here select “On” if RCU is installed.
Selection option Off and On.
- Factory setting: Off
Menu 9.2.17 TL-alarm activated [S]
Settings whether temperature limiter should be “On” or
“Off”.
Selection option Off and On.
- Factory setting: On
Menu 9.2.18 Room sensor type [S]
Room sensor type is selected here. Menu 6.0 can be ac-
cessed.
Selection option From, RG05, RG10 or RE10
- Factory setting: Off
Menu 9.2.19 Return [S]
Pressing the enter button returns you to Menu 9.2.0
Menu 9.3 Quick start [S]
When “On” is selected, the heat pump starts within 5 min-
utes. Returns automatically to “Off”, which indicates that
quick start is activated.
Selection option Off and On.
- Factory setting: Off
Control