ANSI Hardware Installation Manual 7360 ISAM FX-12 shelf cabling
Issue: 09 3HH-12893-AAAA-TCZZA 171
DRAFT
Observe the following safety notes.
10.3.1 Grounding cable type
As shown in Figure 79, the 7360 ISAM FX-12 includes two grounding cable 
connectors. Each ground lug is a 4 AWG, with 1/4 in. holes, with 3/4 in. spacing, 
single crimp, peep, copper, UL and CSA recognized dual-hole lug. The preferred 
cable is 4 AWG, green with a yellow stripe. Other types and sizes of wire and lugs 
can also be used provided they meet the requirements of Article 250 of the NEC.
10.3.2 Cable routing and connection
The grounding cable must be used when the shelf is stand-alone and will not be used 
if the shelf is assembled in a rack. The cable is routed through an opening in the right 
side of the shelf to the grounding terminal.
The connections for the grounding cable are shown in Figure 79. The grounding 
cable is connected to the shelf frame with hardware included with the shelf.
Danger 1 —  Rack or frame must be suitably connected to the 
office grounding network in accordance with Article 250 of the 
national electrical code (NEC) to ensure UL and CSA 
compliance. If outside the United States, ground per local 
electrical codes and practices. 
Danger 2 —  Possible risk of personal injury or damage to 
equipment due to inaccurate or faulty ground cabling.
Inaccurate grounding connection can cause electric shock or 
equipment damage when the rack power is switched on.