42
– Standby operation with anti freeze function
In this operating mode the water in the cylinder is warmed up so far in standby operation that the
water in the cylinder cannot freeze.
Note: the keep warm function works only, if the external safety chain is closed. Therefore this func-
tion may not be used for outdoor operation.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the
upcoming Idle submenu set the parameters for standby operation with anti freeze function.
Settings:
• “Idle Mode”: “A.Freeze”
• “Heat Power”: heating power for anti freeze function (Factory setting: 50 W, Setting range:
10...200 W)
5.3.7.4 Activating/Deactivating the forced draining
Select “Force Drain” in the water management settings submenu, then press the <Set> key.
In the upcoming modication dialogue activate/deactivate the forced draining which takes place after a
certain time of operation (see following setting).
Note: The forced draining takes place also during steam production.
Factory setting: Off
Options: On (Forced draining activated)
Off (Forced draining deactivated)
Water Manag.
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Conductivity:>125µS
Force Delay :72h
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Operat.
Heat Power :50W
Idle Mode :A.Freeze
Esc Set
Idle Operat.
Heat Power :50W
Idle Mode :A.Freeze
Esc Set
Idle Mode
IdleOnly
Drain
KeepWarma
Drain
A.Freeze
Esc Set
Heat Power
50 W
50 W
Esc Set
Water Manag.
Drain Factor:1.0
Idle Operat.:Set
Force Drain :On
Conductivity:>125µS
Force Delay :72h
Esc Set
Force Drain
O
On
On
Esc Set
Settings
Power Limit :100%
Water Manag.:Set
Date :11-08-31
SC-System :Set
Time :12:00
Esc Set
Settings
Power Limit :100%
Water Manag.:Set
Date :11-08-31
SC-System :Set
Time :12:00
Esc Set