7-5
H Time from START Input to Start of Operation
The diagram shows the time from when the START input is turned ON until cam outputs can be con-
trolled.
START input
RUN output
Cam output
Enabled
Disabled
Data Symbol Standard time
RUN output delay time
Td1 10 ms max.
py
Td2 8 ms max.
Cam output delay time
Td3 10 ms max.
py
Td4 8 ms max.
H Origin Shift Processing Time
The diagram shows the time from when TRIG input is turned ON until cam outputs and RUN outputs
change.
TRIG input
RUN output
Cam output
Enabled
Disabled
Data Symbol Standard time
RUN output delay time Td1 15 ms max.
RUN output OFF time Td2 0.8 to 1.2 s
Cam output delay time Td3 15 ms max.
Cam output OFF time Td4 0.8 to 1.2 s
Min. TRIG input enabled time Td5 10 ms min.
Appendix Chapter 7