2-25
H Cam Output Specifications
Item Specifications
Maximum switching capacity 24 V DC –15%/10%, 0.3 A/point, 1.6 A/connector
Leakage current 0.1 mA max.
Residual voltage 1.5 V max.
ON response time 0.05 ms max.
Off response time 0.07 ms max.
Internal circuit
CAM1 to 32
2-3-6 Connecting a Display Unit
If the Cam Positioner is connected to a Display Unit, the present angle and Resolver
speed can be displayed.
The Display Unit is connected to the cam output connectors on the Unit via Cam Output
Cables.
Note 1. The speed display can have an error margin or 5 r/min max.
Note 2. Parameters must be set to display present values such as the present angle
and Resolver speed. The present value output and cam output share termi-
nals. Some cam output signals can no longer be used, therefore, when pres-
ent values are being output.
H Connecting a M7E Display Unit
Use a 3F88L-CGjjjS Cam Output Cable to connect the M7E Display Unit.
3F88L-160/162 Cam Positioner
3F88L-CGjjjS Cam Output Cable
M7E Display Unit
D Functions
The present angle (in degrees) or the Resolver speed (r/min) can be displayed on a 3- or 4-digit Display
Unit. The display data is set using the present value display function parameters.
Design Chapter 2