3-80
Press the Set Key. The data will remain lit for approximately one second, the settings will be confirmed,
and then the data will resume flashing again.
H Data Output Timing
w 3F88L-160 (16-point Model)
w For Present Value Outputs Set to “2” (4-digit Resolver Speed (No Units))
1st digit display 2nd digit display 3rd digit display 4th digit display 1st digit
Output Tr:ON
Output Tr:OFF
Output Tr:ON
Output Tr:OFF
Output Tr:ON
Output Tr:OFF
Output Tr:ON
Output Tr:OFF
Time
Time
Time
Time
Time
Note The output timing for each digit of display data (CAM 13 to 16) and each digit’s LE signal (CAM9 to
12) are shown below.
1st digit display data
3-6-11 Pulse Output Function
H Function
The pulse output function creates cam programs that turn ON and OFF at even intervals at particular
bank and cam numbers.
The cam programs that turn ON/OFF at even intervals can be set from any angle (pulse start position).
Note 1. For pulse settings to be made, the resolution/(pulse number × 2) must be an integer. If this
equation does not produce an integer, the pulse number will be changed to the nearest pulse
number that will give an integer. The pulse numbers are as follows:
For 360 resolution: 1, 2, 3, 4, 5, 6, 9, 10, 12, 15, 18, 20, 30, 36, 45, 60, 90, 180
For 720 resolution: 1, 2, 3, 4, 5, 6, 8, 9, 10, 12, 15, 18, 20, 24, 30, 36, 40, 45, 60, 72, 90, 120,
180, 360
If a pulse that falls between any of these pulse numbers is set, it will be converted to the next
largest pulse number. For example, if “7” is set for 720 resolution, it will be converted to “8.”
Note 2. If the pulse number and pulse start position are set, a cam program that turns ON at the pulse
start position will be created.
Operation Chapter 3