EasyManuals Logo

Omron CP1H CPU User Manual

Omron CP1H CPU
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #274 background imageLoading...
Page #274 background image
240
Pulse Outputs Section 5-3
Stopping a Pulse Output
Operation Example
application
Frequency changes Description Procedure
Instruction Settings
Stop pulse
output
Immediate
stop
Stops the pulse out-
put immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
INI(880)
•Port
•Stop
pulse out-
put
Stop pulse
output
Immediate
stop
Stops the pulse out-
put immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
SPED(885)
(Continu-
ous)
•Port
•Continu-
ous
•Target fre-
quency=0
Stop pulse
output
smoothly
Decelerate
to a stop
Decelerates the
pulse output to a
stop.
Note If ACC(888)
started the
operation, the
original
acceleration/
deceleration
rate will
remain in
effect.
If SPED(885)
started the
operation, the
acceleration/
deceleration
rate will be
invalid and
the pulse out-
put will stop
immediately.
SPED(885)
or ACC(888)
(Continu-
ous)
↓
ACC(888)
(Continu-
ous)
•Port
•Continu-
ous
•Target fre-
quency=0
Pulse frequency
Present frequency
Execution of INI(880)
Time
Pulse frequency
Present frequency
Execution of SPED(885)
Time
Pulse frequency
Present frequency
Execution of ACC(888)
Acceleration/
deceleration rate
(Rate set at the
start of the
operation.)
Target frequency = 0
Time