558
Trouble Shooting Section 9-11
9-11-3 Error Status
The status of errors that occur at the Ethernet Option Board is reflected in CIO
relation area, Refer to 9-9-1 CIO Area Allocation, Error Status for details.
ERR
Indicator
Error Probably Cause Error code
(hex)
Correction
Flashing Address
Disagreement
The node number set
for the option board
does not agree with
the host ID in the IP
address. This proba-
bly occurs when the
address conversion
method is set for auto-
matic address genera-
tion.
021A Make sure that the node number and the last
byte of the IP address are the same and then
set other host IDs to 0.
Change the address conversion method.
Logic error in
setting table
There is a logic error
in the setting table.
021A Recreate the data specified by the 2nd byte
of the detailed error code.
System setup Sum
check error
The Checksum of
System setup is incor-
rect.
03D0 Reset the value of system setup area.
Restart the CPU Unit.
FINS/TCP setting
error
The settings of
FINS/TCP are
incorrect.
03C0 Refer to operation manual and set the
FINS/TCP setting correctly.