3-2 Setting the Routing Tables
3-2-2 Creating the FINS Local Routing Tables
Note
The serial port's CPU SIOU value (unit number) is allocated automatically, so it cannot
be changed. The following FINS unit addresses (decimal) are allocated.
Serial port 1 80 hex + 04 hex ×
unit number
Serial Communications Unit
Serial port 2 81 hex + 04 hex ×
unit number
Serial port 1 E4 hex (228 decimal) Serial Communications Board
Serial port 2 E5 hex (229 decimal)
Peripheral port FD hex (253 decimal) CPU Unit
RS-232C port FC hex (252 decimal)
A Unit and the Unit's serial port cannot be registered in the local network table at the
same time.
Setting the Relay Network Table Online
Set the relay network table for PLC1 online.
1. Click the Table View Tab at the bottom of the PLC Routing Table Window to switch
to the Table View format.
2. Input the destination (remote) network address, relay network address, and relay
node address and click the OK Button.