E5GN
5–35
Output input error
The alarm 1 type must be supported.
The control must be set to standard control.
Ă• When this setting is set to ON", alarm 1 output becomes ON at an input error. Note,
however, that the alarm 1 operation display does not light.
Ă• The alarm 1 output is the ORed output of alarm 1, HBA used and input error.
Ă• Output is turned OFF when the initial setting level, communications setting level,
advanced function setting level or calibration level is switched to.
Setting Range Default
: ON / : OFF
FĂRelated parameter
Input error" (error display) (p. AĆ4)
Cold junction
compensation method
Input type must be thermocouple or non–con-
tact temperature sensor
Ă• Specifies whether cold junction compensation is to be performed internally by the
controller or to be performed externally when the input type setting value is No.0 to
15, 17 or 18.
Ă• The cold junction compensation external setting is valid when the temperature difĆ
ference is measured using two thermocouples or two ESIAs.
Setting Range Default
: internally / : externally
FĂRelated parameter
Input type" (initial setting level) (p. 5Ć16)
Advanced Function Setting Level
Function
Setting
See
Function
Setting
See