CHAPTER 5 PARAMETERS
E5GN
5–30
ST stable range
The control must be set to temperature input,
PID control and ST set to “ON”.
Ă• This parameter sets the set value for determining the conditions under which ST
(selfĆtuning) occurs. This parameter cannot be used when the ST" parameter is set
to OFF".
Setting Range Unit Default
0.1 to 999.9 _C or _F 15.0
FĂRelated parameters
PID / ON/OFF" (initial setting level)
Input type" (initial setting level)
ST" (initial setting level)
α
The control must be 2-PID control, and the
“ST” parameter must be set to “OFF”.
Ă• Normally, use this parameter at its default.
Ă• This parameter sets 2ĆPIDĆconstant α.
Setting Range Unit Default
0.00 to 1.00 None 0.65
FĂRelated parameters
PID / ON/OFF" (initial setting level)
ST" (initial setting level)
Advanced Function Setting Level
Function
Setting
See
Function
Setting
See