CHAPTER 5 PARAMETERS
E5GN
530
ST stable range
The control must be set to temperature input,
PID control and ST set to ON.
Ă This parameter sets the set value for determining the conditions under which ST
(selfĆtuning) occurs. This parameter cannot be used when the ST" parameter is set
to OFF".
Setting Range Unit Default
0.1 to 999.9 _C or _F 15.0
FĂRelated parameters
PID / ON/OFF" (initial setting level)
Input type" (initial setting level)
ST" (initial setting level)
α
The control must be 2-PID control, and the
ST parameter must be set to OFF.
Ă Normally, use this parameter at its default.
Ă This parameter sets 2ĆPIDĆconstant α.
Setting Range Unit Default
0.00 to 1.00 None 0.65
FĂRelated parameters
PID / ON/OFF" (initial setting level)
ST" (initial setting level)
Advanced Function Setting Level
Function
Setting
See
Function
Setting
See