E5GN
5–29
Alarm 1 open in alarm
E5GN-j1j must be used.
Ă• This parameter sets the output states of alarm 1.
Ă• When the E5CN is set to close in alarm," the status of the alarm output function is
normally open. When set to open in alarm," the status of the alarm output is output
inverted, or normally closed. The following table shows the relationship between
alarm output functions, alarm output and output LCDs.
When alarm 1 open in alarm" is set to open in alarm", the heater burnout alarm
and input error output also become open in alarm."
Alarm Output Function Alarm Output Output LCDs
ON ON Lit
Close in alarm
OFF OFF Out
ON OFF Lit
Open in alarm
OFF ON Out
Setting Range Default
: Close in alarm / : Open in alarm
FĂRelated parameters
Alarm value 1" UpperĆlimit alarm value 1" LowerĆlimit alarm value 1" (operation
level)
Alarm 1 type" (initial setting level)
Alarm 1 hysteresis" Standby sequence reset method" Alarm 1 latch" (advanced
function setting level)
Alarm 1 hysteresis
E5GN-j1j must be used.
Ă• This parameter sets the hysteresis of alarm output 1.
Ă• During analog input, the decimal point setting follows the decimal point position"
setting.
Setting Range Unit Default
0.1 to 999.9 _C or _F 0.2
FĂRelated parameters
Alarm value 1" UpperĆlimit alarm value 1" LowerĆlimit alarm value 1" (operation
level)
Alarm 1 type" (initial setting level)
Alarm 1 open in alarm" Standby sequence reset method" Alarm 1 latch"
(advanced function setting level)