2-625
2 Instruction Descriptions
NJ-series Instructions Reference Manual (W502)
System Control Instructions
2
ResetCJBError
The following example is for when UnitNo is _CBU_No00. The Controller error on the I/O bus is reset
and the CPU Bus Unit with unit number 0 is restarted.
The error may not be reset immediately after you execute this instruction. Use the GetCJBError
instruction to confirm that the errors were reset.
An error occurs in the following cases. ENO will be FALSE.
The value of UnitNo is outside of the valid range.
The Unit specified by UnitNo does not exist.
Related System-defined Variables
Name Meaning Data type Description
_CJB_ErrSta I/O Bus Error Status WORD Contains the error status of the I/O bus.
Refer to the NJ-series CPU Unit Software
User's Manual (Cat. No. W501) for details.
Precautions for Correct Use
ResetCJBError_instance(A, _CBU_No00,
abc, def, ghi, jkl);
LD
ST
_CBU_No00
A
ResetCJBError
ResetCJBError_instance
def
ghi
jkl
abc
EN Done
UnitNo Busy
Error
ErrorID