2-709
2 Instruction Descriptions
NJ-series Instructions Reference Manual (W502)
Communications Instructions
2
CIPUCMMRead
The value of Size is outside of the valid range.
The value of DstDat is outside of the valid range.
The value of RcvSize is outside of the valid range.
For this instruction, expansion error code ErrorIDEx gives the CIP message error code. The mean-
ings are as follows:
Refer to the sample programming that is provided for the CIPUCMMSend instruction (page 2-716).
Value Error
16#02000000 Normal communications are not possible due to a high load at the remote node.
16#05000000 The specified source variable does not exist on the other Controller.
16#0C008010 The specified source variable is being downloaded.
16#0C008011
16#11000000 The value of Size is exceeds the data size that can currently be read.
16#20008017 The specified source variable is not an array and the number of elements to read is not 1.
16#20008018 The specified source variable is an array and the number of elements to read exceeds the
number of elements in the array.
16#26000000 The specified destination variable contains only the NULL character.
Sample Programming