5-10
Speed Search: b3
b2-09
Motor preheat
current 1
Sets the motor preheat current level
in % of the Inverter rated current.
Motor preheat is enabled by an dig-
ital input.
0 to
100
0% No A 1E1H 6-106
b2-10
Motor preheat
current 2
Sets the motor preheat current level
2 in % of the Inverter rated current.
Motor preheat 2 is enabled by an
digital input.
0 to 10 5% No A 61CH 6-106
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
b3-01
Speed search
selection (current
detection or
speed calcula-
tion)
Enables/disables the speed search
function and sets the speed search
method.
0:Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the
motor speed is calculated and
acceleration/deceleration is per-
formed from the calculated speed
to the specified frequency (motor
direction is also searched).
Current Detection:
The speed search is started from
the frequency when power was
momentarily lost and the maxi-
mum frequency, and the speed is
detected at the search current level.
0 to 3 2 No A 191H 6-39
b3-02
Speed search
operating current
(current detec-
tion)
Sets the speed search operation
current as a percentage, taking the
Inverter rated current as 100%.
Usually not necessary to set. When
restarting is not possible with the
factory settings, reduce the value.
0 to
200
120% No A 192H 6-39
b3-03
Speed search
deceleration time
(current detec-
tion)
Sets the output frequency decelera-
tion time during speed search in 1-
second units.
Sets the time for deceleration from
the maximum output frequency to
the minimum output frequency.
0.1 to
10.0
2.0 sec. No A 193H 6-39
b3-05
Speed search wait
time (current
detection or
speed calcula-
tion)
When a speed search is performed
after recovering from a momen-
tary power loss, the search opera-
tion is delayed for the time set here.
If e.g. a contactor is used at the out-
put side of the inverter set this
parameter to the contactor delay
time or more.
0.0 to
20.0
0.2 sec. No A 195H 6-39
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page

Table of Contents