5-28
MEMOBUS Communications: H5
Param-
eter
Number
Name Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
MEMO-
BUS
Register
Page
H5-01 Station address Sets the Inverter's node address.
0 to 20
*1
*1. Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications
1F No A 425H 6-69
H5-02
Communications
speed selection
Sets the baud rate for MEMOBUS
communications.
0:1200 bps
1:2400 bps
2:4800 bps
3:9600 bps
4:19200 bps
0 to 4 3 No A 426H 6-69
H5-03
Communications
parity selection
Sets the parity for MEMOBUS
communications.
0:No parity
1:Even parity
2:Odd parity
0 to 2 0 No A 427H 6-69
H5-04
Stopping method
after communica-
tions error
Sets the stopping method for com-
munications errors.
0:Deceleration to stop using the
deceleration time in C1-02
1:Coast to stop
2:Emergency stop using the
deceleration time in C1-09
3:Continue operation
0 to 3 3 No A 428H 6-69
H5-05
Communications
error detection
selection
Sets whether or not a communica-
tions time out is to be detected as a
communications error.
0:Not detected
1:Detect
0 or 1 1 No A 429H 6-69
H5-06 Send wait time
Sets the time the Inverter waits
until a response is sent to the Mas-
ter.
5 to 65 5 msec No A 42AH 6-69
H5-07
RTS control ON/
OFF
Enables or disables RTS control.
0: Disabled (RTS is always ON)
1: Enabled (RTS turns ON only
when sending)
0 or 1 1 No A 42BH 6-69
H5-08
Communication
Selection
Selects the Protocol for the Com-
munication
0: Memobus
1: N2 (Metasys)
0, 1 0 No A 434H 6-69
H5-09 CE detection time
Sets the time before CE error
(Communication error) is detected
when MEMOBUS communication
is used.
0.0 to
10.0
sec
2.0 sec No A 435H 6-69