User Parameter Tables
5-49
400 V Class Inverters in Protection Class IP54
Parame-
ter Num-
ber
Name Unit Factory Setting
– Inverter Capacity kW 160 185 220 300
o2-04 kVA selection – 34 35 36 37
b8-04 Energy-saving coefficient – 30.13 30.57 27.13 21.76
C6-02
Carrier frequency
selection
*1
Normal Duty 1 –2211
Normal Duty 2–2111
E2-01 Motor rated current A 270.0 310.0 370.0 500.0
E2-03 Motor no-load current A 70.0 81.0 96.0 130.0
E2-05 Motor line-to-line resistance W 0.029 0.025 0.020 0.014
L2-02 Momentary power loss ride through time sec. 2.0 2.0 2.0 2.0
L2-03 Min. baseblock (BB) time sec. 1.8 1.9 2.0 2.1
L2-04 Voltage recovery time sec. 1.0 1.0 1.0 1.0
L8-02 Overheat pre-alarm level °C 108 95 100 108
L8-06 Input phase loss detection level % 14.0 15.0 15.0 15.0
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier
frequency is set higher than the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will
need to be reduced.
Parame-
ter Num-
ber
Name Unit Factory Setting
– Inverter Capacity kW 7.5 11 15 18.5 22 30 37 45 55
o2-04 kVA selection – 67 68 69 6A 6B 6C 6D 6E 6F
b8-04 Energy-saving coefficient –
145.38 140.88 126.26 115.74 103.58 92.54 76.32 71.56 67.20
C6-02
Carrier frequency selection
*1
*1. The initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10 kHz, 5: 12.5 kHz, and 6: 15 kHz. If the carrier frequency is set higher than
the factory setting for Inverters with outputs of 30 kW or more, the Inverter rated current will need to be reduced.
–222222222
E2-01 Motor rated current A
13.30 19.9 26.5 32.9 38.6 52.3 65.6 79.7 95.0
E2-03 Motor no-load current A
4.00 5.6 7.6 7.8 9.2 10.9 19.1 22.0 24.0
E2-05 Motor line-to-line resistance W
1.152 0.922 0.550 0.403 0.316 0.269 0.155 0.122 0.088
L2-02
Momentary power loss ride
through time
sec.
0.81.02.02.02.02.02.02.02.0
L2-03 Min. baseblock (BB) time sec.
0.70.80.91.01.01.11.11.21.2
L2-04 Voltage recovery time sec.
0.30.30.30.60.60.60.60.61.0
L8-02 Overheat pre-alarm level °C
90 95 95 98 87 87 85 86 86
L8-06 Input phase loss detection %
20.0 23.0 17.0 17.0 20.0 20.0 20.0 20.0 20.0