6-88
Related Parameters
Parameter
Number
Name
Setting
Range
Factory
Setting
Change
during
Operation
Access
Level
b5-01 PI control mode selection 0, 1, 3 0 No A
b5-02 Proportional (P) gain
0.00
to
25.00
1.00 Yes
A
*1
*1. Parameter is moved into Quick Programming Mode when PI controller is enabled, otherwise the parameter is available only in Advanced
Programming Mode
b5-03 Integral (I) time
0.0 to
360.0
1.0 sec. Yes
A
*1
b5-04 Integral (I) limit
0.0 to
100.0
100.0% Yes A
b5-06 PI limit
0.0 to
100.0
100.0% Yes A
b5-07 PI offset
-100.0
to
+100.0
0.0% Yes A
b5-08 PI delay time constant
0.00 to
10.00
0.00 sec. Yes A
b5-09 PI output characteristics selection 0 or 1 0 No A
b5-10 PI output gain
0.0 to
25.0
1.0 No A
b5-11 PI reverse output selection 0 or 1 0 No A
b5-12 Selection of PI feedback signal loss detection 0 to 2 0 No A
b5-13 PI feedback loss detection level 0 to 100 0% No A
b5-14 PI feedback loss detection time
0.0 to
25.5
1.0 sec. No A
b5-15 Sleep function operation level
0.0 to
200.0
0.0 Hz No A
b5-16 Sleep operation delay time
0.0 to
25.5
0.0 sec. No A
b5-17 Accel/decel time for PI reference
0.0 to
25.5
0.0 sec. No A
b5-18 PI Setpoint Selection 0 to 1 0 No A
b5-19 PI Setpoint
0.00 to
100.00
0% Yes A
b5-20 PI Setpoint Scaling
0 to
39999
1NoA
b5-21 Sleep Function Selection 1 to 2 1 No A
b5-22 Snooze Level 0 to 100 0% Yes A
b5-23 Snooze Delay Time 0 to 3600 0 sec. No A
b5-24 Wake-Up Level 0 to 100 0% No A
b5-25 Setpoint Boost 0 to 100 0% No A
b5-26 Maximum Boost Time 0 to 3600 0 sec. No A
b5-27 Snooze feedback 0 to 100 60% No A
b5-28 PI Feedback Square Root Operation 0 or 1 0 No A
b5-29 PI Feedback Square Root Gain 0 to 2.00 1.00 No A
b5-30 PI Output Monitor Square Root 0 or 1 0 No A
b5-31 PI unit selection 0 to 11 0 No A