32
Parameter
Parameter name Setting range Factory setting Update
Reference
page
Alarm and information settings
INFO action (Driver temperature information
(INFO-DRVTMP))
0: INFO action is not applied
Information bit output:
Applied
• INFO output: Not applied
• LED: Not applied
1: INFO action is applied
Information bit output:
Applied
• INFO output: Applied
• LED: Applied
1 A P.41
INFO action (Overvoltage information (INFO-OVOLT))
INFO action (Undervoltage information (INFO-
UVOLT))
INFO action (Load information (INFO-LOAD))
INFO action (Speed information (INFO-SPD))
INFO action (Operation data setting error information
(INFO-SET-E))
INFO action (Operation prohibited information
(INFO-DRV))
INFO action (RS-485 communication error information
(INFO-NET-E))
INFO action (Rotation amount meter information
(INFO-REV))
INFO action (Tripmeter information (INFO-TRIP))
INFO action (Odometer information (INFO-ODO))
INFO action (Torque limiting value setting error
information (INFO-TRQ-DE))
INFO action (Rotation speed setting error information
(INFO-SPD-DE))
INFO action (Main power supply time information
(INFO-PTIME))
INFO action (Main power supply count information
(INFO-PCOUNT))
INFO action (Operation start limit mode information
(INFO-DSLMTD))
INFO action (I/O test mode information (INFO-
IOTEST))
INFO action (Conguration request information
(INFO-CFG))
INFO action (Power cycling request information
(INFO-RBT))
Monitor setting
Driver user name Up to 16 characters –
A P.44
Speed reduction ratio 100 to 9999 100
Speed reduction ratio digit setting
0: ×1
1: ×0.1
2: ×0.01
2
Speed increasing ratio 1.00 to 2.00 1.00
Direct-IN function selection
Direct-OUT function selection
D-IN0 input function selection
Refer to p.58.
58: FWD (START/STOP)
*
C P.45
D-IN1 input function selection 59: REV (RUN/BRAKE)
*
D-IN2 input function selection 72: STOP-MODE (FWD/REV)
*
D-IN3 input function selection 64: M0
D-IN4 input function selection 8: ALM-RST
D-IN0 input logic level setting
0: Not invert
1: Invert
0: Not invert
D-IN1 input logic level setting 0: Not invert
D-IN2 input logic level setting 0: Not invert
D-IN3 input logic level setting 0: Not invert
D-IN4 input logic level setting 0: Not invert
D-OUT0 output function selection
Refer to p.58.
147: SPEED-OUT
D-OUT1 output function selection 130: ALM-B
D-OUT0 output logic level setting
0: Not invert
1: Invert
0: Not invert
D-OUT1 output logic level setting 0: Not invert
*
If the 3-wire mode is selected with the "Operation input mode selection" parameter, the signal in the parentheses ( ) will be applied.