OID Name Default Value
Range
Note
Min Max
19.xx13.22 Delay Req Rate - 1/16 128
19.xx13.24 PTP Timescale PTP
19.xx13.56 Sync-E Disabled
Power Profile: IEEE C37.238-2011
This profile has been created to target Power Systems Applications.
OID Name
Default
Value
Range
Note
Min Max
19.xx13.x net/<iface>/1/cfg
19.xx13.9 Transport
Protocol
Layer 2
(IEEE802.3)
VLAN tags (IEEE802.1Q) are mandatory, with a
default priority of 4, and default VLAN ID of 0.
19.xx13.10 Delay
Mechanism
P2P
19.xx13.14 Domain 0 0 127
19.xx13.11 Transport
Mode
Multicast
19.xx13.20 Announce
Rate
1
19.xx13.21 Sync Rate 1
19.xx13.23 Peer Delay
req Rate
1
19.xx13.24 PTP Times-
cale
PTP
19.xx13.56 Sync-E Disabled
5.4.3 Info/Overview
Each PTP port runs its own PTP instance independently on a specific process. The inform-
ation about the instance can be obtained from command line, using for example the fol-
lowing command for the first port (wr0):
gpa_ctrl wptpd net/wr0/1/info/
Or through the web interface as shown below, where each port is displayed by a row (see
the table "PTP information for a port interface" on the next page for more details on the
provided parameters).
5.4 IEEE 1588-2008 (PTPv2)
CHAPTER 5 WR-Z16 User Manual Rev. v3.4