12-136
Error
code
Name
Opera-
tion
status
Description and steps to take
FP0
FP-e
FP
Σ
FP-X
FP1/FP-M
FP2
FP2SH
FP10SH
FP3
E41
Intelligent
unit error
Selec-
table
An abnormality in an intelligent unit.
FPΣ, FP-X:
Check the contetns of special data
register “DT90006” and locate the
abnormal FP intelligent unit (application
cassette for FP-X).
FP2,FP2SH,and FP10SH:
Check the contents of special data
registers DT90006,DT90007 and locate
the abnormal intelligent unit.Then check
the unit referring to its manual..
Selection of operation status using
system register22:
-to continue operation,set 1
-to stop operation,set 0
FP3:
Check the contents of special data
registers DT9006,DT9007 and locate the
abnormal intelligent unit.Then check the
unit referring to its manual..
Selection of operation status using
system register22:
-to continue operation,set 1
-to stop operation,set 0
Verification is possible in FPWIN GR/Pro
at”I/O error” in the status display
function.
AA AAAA
E42
I/O unit
verify error
Selec-
table
I/O unit(Expansion unit) wiring condition
has changed compared to that at time fo
power-up.
Check the contents of special data
register (FP0: DT9010,
FPΣ, FP-X: DT90010,DT90011) and
locate the erroneous expansion unit.
It checks whether an expansion
connector is in agreement.
Check the contents of special data
register (FP2,FP2SH,and
FP10SH:DT90010,DT90011,FP3
DT9010,DT9011)
Selection of operation status using
system register23:
-to continue operation,set 1
-to stop operation,set 0
Verification is possible in FPWIN GR/Pro
at”I/O error” in the status display
function.
AAAAAAA
A:Available