Program start temperature
When Program control starts, it starts from the value set in [Program start temperature].
Factory default value is 0 .
Program control start type
One type can be selected: PV start, PVR start, SV start.
Factory default value is PV start.
Program control
start type
Description
PV start
When Program control starts, the SV and step time are advanced to the PV,
then Program control starts.
However, if [Program start temperature] at the time of Program control start is
higher than the PV when PV start is initiated, then Program control will start
from the SV set in [Program start temperature].
PVR start In pattern repeating, the SV and step time are advanced to the PV, then the
Program control starts.
SV start Program control starts from the SV which has been set in [Program start
temperature].
[SV start] [PV/PVR start]
(Fig. 8.7-4) (Fig. 8.7-5)
Repeat function
When Program control is finished, control can be repeated from Step 1.
The user determines the number of repetitions.
Factory default value is 0 (zero).