EasyManua.ls Logo

Parker AC15 Series - Power Stack Wiring (Frame 5)

Parker AC15 Series
125 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC-0017-03-EN: AC15 Series - Hardware Installation Manual
22 (125) DOC-0017-03-EN-B 04.04.2023
Frame 5:
Label
Description
PE
Protective Earth
L1
Supply Input Phase L1
L2
Supply Input Phase L2
L3
Supply Input Phase L3
DC+
DC+ / Dynamic Brake Resistor Connection (+)
DC-
DC-
DBR
Dynamic Brake Resistor Connection (-)
U
Motor Output Phase U
V
Motor Output Phase V
W
Motor Output Phase W
Inverter Connections
AC Line Input Connections:
Incoming AC line supply connections should be wired into terminals:
- L ‘Live’ & N ’Neutral’ on single phase products (15G-1x-…)
- L1, L2 & L3 on three phase products (15G-3x-… & 15G-4x-…)
On three phase products, phase rotation is not critical.
AC Motor Output Connections:
Output motor supply connections should be wired into terminals U, V & W.
Phase rotation is critical to ensure consistency between the inverter motor control direction and motor shaft
rotation.
The motor direction can be inverted electronically by setting the ‘IM Wiring’ parameter (0182) to ‘1’ (TRUE).
This swaps output phases V & W in the drive firmware. Refer to ‘Chapter 9: Basic Drive Operation’.
Potential Earth (PE) Connections:
Connect both the inverter incoming supply earth cable and motor earth cable to the inverter PE terminals.
DC Dynamic Brake Output Connections:
Where a Dynamic Brake Resistor (DBR) is required for an inverter application, connect the resistor across
terminals DC+ & DBR.
Wiring Example
V
S
= AC Voltage
Source:
· 1ø, 220-240V
· 3ø, 220-240V
AC Line
Fuses
Dynamic
Braking
Resistor
3ø Induction or
PMAC Motor

Table of Contents

Related product manuals