EasyManuals Logo

PCME STACK 990 User Manual

PCME STACK 990
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
- PCME STACK 990 MANUAL: 19 -
Set address switch (SW100)
Each sensor must have a unique address on the network. The address is set by means of the DIP
switch (SW100). Only switch positions 1 to 6 are used giving valid address settings from 1 to 64.
The illustration above shows address 5. The address switch uses binary coding to calculate the
required address.
For example, to set address number 5: Set switch 1 (binary 1) ON and switch 3 (binary 4) ON (4
+ 1 = 5).
Communication Settings (SW101)
The sensor has two comms settings, ASCII and RTU. The default setting is ASCII: 19200 Baud,
No Parity, 1 Stop Bit, ASCII mode (7-bit). The DIP switch should be set as follows:
RTU is a faster communications protocol but is not available for all devices; refer to the Control
Unit Reference Manual. If RTU mode is required set the DIP switch as follows:
Refit the Sensor Cover and secure with the four screws. Do not over tighten the screws.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PCME STACK 990 and is the answer not in the manual?

PCME STACK 990 Specifications

General IconGeneral
BrandPCME
ModelSTACK 990
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals