pH > 7.67-OFF 7.50s
ORP 490 -OFF 700s
Heater 68.-OFF 77.0s
SW1OFFSW2OFF
Main Status Screen
Name:Main Pool
System
>Programming
Service
Data ( 8:441 )
Communications
Security Setup
Wizards
Serial # 123456
Configuration Menu, Programming
AK110 Programming Screen Navigation, Heater
EnterBack
1:pH, Mix Time
2:ORP, Mix Time
>3:Heater
A:Alarm
P:Pager1
P:Pager2
P:Pager3
P:Pager4
Programming Setup Screen
Heater, Manual Cycle Time
EnterBack
Enter new value
Current: 00:02:00
00:02:00
v-Cancel ^
Manual Cycle Time Screen
Use the keypad to enter the manual
heater on-time duration.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter
Enter
Enter new value
Current: 77.0
77.0
v-Cancel ^
Press the [Enter] key to make the
heater operation dependent or
independent of the status of the flow
switch SW1.
Note:
The relay 3 programming menu
appears in this format only when
relay 3 has been configured for
"Heater" control.
Heater, Low Temperature Setpoint
Enter
Heater, Minimum Time On
Heater, Minimum Time Off
Enter new value
Current: 00:01:00
00:01:00
v-Cancel ^
Use the keypad to enter the time
delay between the setpoint trigger
and the heater cycle start.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Use the keypad to enter the low
temperature setpoint for heater
control.
Press the [Enter] key to confirm or
the down arrow key to cancel.
On Delay Screen
Low Temperature Setpoint Screen
ManualTime 00:02:00
On If Temp< 77.0
Off if Sw1 Off-NO <
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00<
On If Temp< 77.0
Off if Sw1 Off-YES
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00
On If Temp< 77.0<
Off if Sw1 Off-YES
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00
On If Temp< 77.0
Off if Sw1 Off-YES <
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00
On If Temp< 77.0
Off if Sw1 Off-YES
On DELAY 00:01:00<
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00<
On If Temp< 77.0
Off if Sw1 Off-YES
On DELAY 00:01:00
MinTime On 00:02:00<
MinTimeOff 00:02:00
Overfeed 05:00:00
ManualTime 00:02:00
On If Temp< 77.0
Off if Sw1 Off-YES
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00<
Overfeed 05:00:00
ManualTime 00:02:00
On If Temp< 77.0
Off if Sw1 Off-YES
On DELAY 00:01:00
MinTime On 00:02:00
MinTimeOff 00:02:00
Overfeed 05:00:00<
Heater, Off if SW1 is Off Heater, Independent of SW1
Enter
Heater, On Delay
Enter
Enter new value
Current: 00:02:00
00:02:00
v-Cancel ^
Use the keypad to enter the
minimum amount of time the heater
will be turned on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Minimum Time On Screen
Enter
Enter new value
Current: 00:02:00
00:02:00
v-Cancel ^
Minimum Time Off Screen
Use the keypad to enter the amount
of time the heater will be held off
before it is allowed to turn on again.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter new value
Current: 05:00:00
05:00:00
v-Cancel ^
Overfeed Screen
Use the keypad to enter the daily
maximum accumulated heater on-
time.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Back
AK110 Programming Screen Navigation, Heater, Rev 3 22 Aug 2008