Pentair AK110 - PROGRAMMING SCREEN NAVIGATION: FRONT PANEL ALARM (2 of 2)

Pentair AK110
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
97
pH > 7.67-OFF 7.50s
ORP 490 -OFF 700s
Alarm Out -OFF
69.0f SW1OFFSW2OFF
Main Status Screen
Name:Main Pool
System
>Programming
Service
Data ( 8:441 )
Communications
Security Setup
Wizards
Serial # 123456
Configuration Menu, Programming
AK110 Programming Screen Navigation, Front Panel Alarm (1 of 2)
EnterBack
1:pH, Mix Time
2:ORP, Mix Time
3:Not Used
>A:Alarm
P:Pager1
P:Pager2
P:Pager3
P:Pager4
Programming Setup Screen
EnterBack
Alarm, On if SW1 is Off
Alarm, Low ORP Setpoint
Alarm, Not On if SW1 is Off
Enter
Enter new value
Current: 630
630
v-Cancel ^
Use the keypad to enter the low
ORP value under which the front
panel alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Enter
Low ORP Setpoint Screen
Enter
Alarm, High pH Setpoint
Enter new value
Current: 8.00
8.00
v-Cancel ^
Use the keypad to enter the high pH
value over which the front panel
alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
High pH Setpoint Screen
Alarm, High ORP Setpoint
Enter
High ORP Setpoint Screen
On if Sw1 Off-YES <
On If ORP< 630
On If ORP> 770
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
On if Sw1 Off-NO <
On If ORP< 630
On If ORP> 770
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
On if Sw1 Off-YES
On If ORP< 630<
On If ORP> 770
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
Press the [Enter] key to choose
whether the front panel alarm
indicator is turned on when the flow
switch SW1 is off.
Enter new value
Current: 770
770
v-Cancel ^
Use the keypad to enter the high
ORP value over which the front
panel alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
On if Sw1 Off-YES
On If ORP< 630
On If ORP> 770<
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
On if Sw1 Off-YES
On If ORP< 630
On If ORP> 770
On If pH> 8.00<
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
Enter
Alarm, Low pH Setpoint
Enter new value
Current: 7.00
7.00
v-Cancel ^
Use the keypad to enter the low pH
value under which the front panel
alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Low pH Setpoint Screen
On if Sw1 Off-YES
On If ORP< 630
On If ORP> 770
On If pH> 8.00
On If pH< 7.00<
On If Temp< 32.0
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
Enter
Alarm, Low Temperature Setpoint
Enter new value
Current: 32.0
32.0
v-Cancel ^
Use the keypad to enter the low
temperature under which the front
panel alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
Low Temperature Setpoint Screen
On if Sw1 Off-YES
On If ORP< 630
On If ORP> 770
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0<
On If Temp> 104.0
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
Enter
Alarm, High Temperature Setpoint
Enter new value
Current: 104.0
104.0
v-Cancel ^
Use the keypad to enter the high
temperature over which the front
panel alarm indicator will turn on.
Press the [Enter] key to confirm or
the down arrow key to cancel.
High Temperature Setpoint Screen
On if Sw1 Off-YES
On If ORP< 630
On If ORP> 770
On If pH> 8.00
On If pH< 7.00
On If Temp< 32.0
On If Temp> 104.0<
Off if Sw1 Off-NO
On if Sw2 On –NO
On if Sw2 Off-NO
On If Overfeed YES
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
To Front Panel Alarm (2 of 2)
Note:
The options available on the Front
Panel Alarm Screen programming
menu may vary in accordance with
the chosen configurations for relays
1, 2 and 3.
Back
AK110 Programming Screen Navigation, Front Panel Alarm, Rev 3 22 Aug 2008