32 - ATR244 - User manual
48 
a.ma.1
  Automatic / Manual 1
Enables the automatic/manual selection for command 1
diS a b.
  Disabled (Default)
Enab.
 Enabled
En.Sto.
  Enabled with memory
49÷53  Reserved Parameters - Group C
Reserved parameters - Group C
GROUP D - 
cmd.2
 - Outputs and regulation Process 2
54 
c.ou.2
  Command Output 2 (only on ATR-ABC-T)
Selects the command output related to the process 2
diS a b.
  Command disabled. (Default)
c. o3
  Command on relay output Q3
c. SS r
  Command on digital output DO2
c. vA L
. 
Sevo-valve command with open loop on DO1 (open) and DO2 (close)
c. 0 .-1 0
  Command 0-10 V on analogue output AO2
c.4 - 2 0
  Command 4-20 mA on analogue output AO2
55 
c.Pr.2
  Command Process 2 (only on ATR-ABC-T)
Selects process value related to process 2 and to command output 2.
A.i n .1
  Value read on input AI1. (Default)
A.i n . 2
  Value read on input AI2.
MEAn
  Arithmetic average of the value read on inputs AI1 and AI2 [(AI1-AI2)/2].
d i F F.
  Difference of the values read on inputs AI1 and AI2 (AI1-AI2).
A b . d i f.
  Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|).
SuM
   Sum of values read on inputs AI1 and AI2 (AI1+AI2).
56 
rEM.S.
  Remote Setpoint (only on ATR-ABC-T)
Enables remote setpoint. The control setpoint is sent by another device and is received by a 
second analogue input (it is necessary to select on parameter 
c. p r.2 the selections Ai .  1 or A.i . 2.) 
or through serial.
diS a b.
  Disabled. (Default)
Enab.
  Enables remote setpoint by process 2. Remote/local selection can be done by digital 
input.
En.tS t.
  Remote setpoint by process 2, Remoto/local selection only by keyboard (not allowed 
by digital input)
E n.S e r.
  Enables remote setpoint by serial input. Remote/local selection can be done by digital 
input.
E n.S e.t.
  Remote setpoint by serial, Remote/local selection only by keyboard (not allowed by 
digital input).
cmd . 1  The reference setpoint of command 2 is the same of command 1.
57 
Ac. t.2
  Action type 2
Action type to control process 2.
HEAt
  Heating (N.A.) (Default)
cooL
  Cooling (N.C.)
58 
c.HY.2
  Command Hysteresis 2
Hysteresis to control process 2 in ON/OFF.
-9999..+9999 [digit
1 p. 65
] (degrees.tenths for temperature sensors). Default 0.2.
59 
L.L.S.2
  Lower Limit Setpoint 2
Lower limit setpoint selectable for command setpoint 2.
-9999..+30000 [digit
1 p. 65
] (degrees for temperature sensors). Default 0.