User manual - ATR244 - 55
GROUP Q - 
sft.s
 - Soft-start and mini cycle
263 
Pr. cY.
  Pre-programmed Cycle
Enables special functionings.
diS a b.
  Disabled (Default)
Enab.
  Enabled (all remote sepoint functions are inhibited)
264 
SS.TY.
  Soft-Start Type
Enables and selects the soft-start type
diS a b.
  Disabled (Default)
Grad.
 Gradient
P erc.
  Percentage (only with pre-programmed cycle disabled)
265 
ss.r.c.
  Soft-Start Reference Command (only on ATR-ABC-T)
Defines the reference command for the Soft-Start and the pre-programmed cycle.
cmd. 1
  Command 1 (Default)
cmd. 2
  Command 2
c m d.1. 2
  Command 1 and 2
266 
SS. G r.
  Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
0..20000 Digit/ora (gradi.decimo/ora se temperatura). (Default: 100.0)
267 
SS.Pe.
  Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (Default: 50%)
268 
SS. tH.
  Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-9999...30000 [digit
1 p. 65
] (degrees.tenths for temp. sensors) (Default: 1000)
269 
SS . ti .
  Soft-Start Time
Max. Softstart duration: if the processs will not reach the threshold selected on par. 
SS. tH. within 
the selected time, the controller starts to regulate on setpoint.
00:00 Disabled
00:01-24:00 hh:mm (Default: 00:15)
270 
M A . ti .
  Maintenance Time
Maintenance time for pre-programmed cycle.
00:00-24:00 hh.mm (Default: 00:00)
271 
FA. G r.
  Falling Gradient
Falling gradient for pre-programmed cycle.
0  Disabled (Default)
1..10000 Digit/ora
1 p. 65
 (degrees.tenths/hour if temperature)
272÷276  Reserved Parameters - Group Q
Reserved parameters - Group Q