EasyManua.ls Logo

Pixsys ATR244 - Pre-Programmed Cycle; Soft-Start Type; Soft-Start Reference Command; Soft-Start Gradient

Pixsys ATR244
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User manual - ATR244 - 55
GROUP Q -
sft.s
- Soft-start and mini cycle
263
Pr. cY.
Pre-programmed Cycle
Enables special functionings.
diS a b.
Disabled (Default)
Enab.
Enabled (all remote sepoint functions are inhibited)
264
SS.TY.
Soft-Start Type
Enables and selects the soft-start type
diS a b.
Disabled (Default)
Grad.
Gradient
P erc.
Percentage (only with pre-programmed cycle disabled)
265
ss.r.c.
Soft-Start Reference Command (only on ATR-ABC-T)
Defines the reference command for the Soft-Start and the pre-programmed cycle.
cmd. 1
Command 1 (Default)
cmd. 2
Command 2
c m d.1. 2
Command 1 and 2
266
SS. G r.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
0..20000 Digit/ora (gradi.decimo/ora se temperatura). (Default: 100.0)
267
SS.Pe.
Soft-Start Percentage
Output percentage during soft-start function.
0..100%. (Default: 50%)
268
SS. tH.
Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-9999...30000 [digit
1 p. 65
] (degrees.tenths for temp. sensors) (Default: 1000)
269
SS . ti .
Soft-Start Time
Max. Softstart duration: if the processs will not reach the threshold selected on par.
SS. tH. within
the selected time, the controller starts to regulate on setpoint.
00:00 Disabled
00:01-24:00 hh:mm (Default: 00:15)
270
M A . ti .
Maintenance Time
Maintenance time for pre-programmed cycle.
00:00-24:00 hh.mm (Default: 00:00)
271
FA. G r.
Falling Gradient
Falling gradient for pre-programmed cycle.
0 Disabled (Default)
1..10000 Digit/ora
1 p. 65
(degrees.tenths/hour if temperature)
272÷276 Reserved Parameters - Group Q
Reserved parameters - Group Q