User manual - ATR244 - 61
GROUP V -
s e r.
- Seriale
318
sL. a d .
Slave Address
Selects slave address for serial communication.
1...254. Default: 247.
319
bd . rt.
Baud Rate
Selects baudrate for serial communication
1. 2 k
1200 bit/s
2.4 k
2400 bit/s
4.8 k
4800 bit/s
9.6 k
9600 bit/s
19.2 k
19200 bit/s (Default)
28.8 k
28800 bit/s
3 8 .4 k
38400 bit/s
57.6 k
57600 bit/s
115. 2 k
115200 bit/s
320
s. p. p.
Serial Port Parameters
Selects the format for the modbus RTU serial communication.
8-N-1
8 bit, no parity, 1 stop bit (Default)
8- E-1
8 bit, even parity, 1 stop bit
8-o-1
8 bit, odd parity, 1 stop bit
8-N-2
8 bit, no parity, 2 stop bit
8-E-2
8 bit, even parity, 2 stop bit
8-o-2
8 bit, odd parity, 2 stop bit
321
se. de.
Serial Delay
Selects serial delay
0...100 ms. Default: 5 ms.
322
o ff.L.
Off Line
Selects the off-line tine. If there is no serial communication during the selected time, the
controller switches-off the command output.
0 Offline disabled (Default)
0.1-600.0 tenths of second.
323÷327 Reserved Parameters - Group V
Reserved parameters - Group V