60 - ATR244 - User manual
GROUP U -
a. o. 2
- Retransmission 2
308
rtM.2
Retransmission 2
Retransmission for output AO2. Parameters 310 and 311 define lower and upper limit of the
operating scale.
diS a b.
Disabled (Default)
c.1.S Pv
Command 1 setpoint
A L. 1
Alarm 1 setpoint
A L. 2
Alarm 2 setpoint
Md.b us
Retransmits the value written on word 1242
A.iN.1
Value read on input AI1
A.i n . 2
Value read on input AI2
MEAn
Arithmetic average of the value read on inputs AI1 and AI2 [(AI1+AI2)/2]
d i F F.
Difference of the values read on inputs AI1 and AI2 (AI1-AI2)
A b . d i f.
Module of the difference of the values read on inputs AI1 and AI2 (|AI1-AI2|)
SuM
Sum of values read on inputs AI1 and AI2 (AI1+AI2)
c.2.S Pv
Command 2 setpoint
AMPer.
Ampere from current transformer
309
r.2. t y .
Retransmission 2 Type
Selects the retransmission type for AO2
0.1 0 v
Output 0...10 V.
4.20 ma
Output 4...20 mA. Default
310
r.2. L.L.
Retransmission 2 Lower Limit
Retransmission 2 lower limit range (value related to 10 V or 0/4 mA).
-9999..+30000 [digit
1 p. 65
] (degrees if temperature), Default: 0.
311
r.2. u .L.
Retransmission 2 Upper Limit
Retransmission 2 upper limit range 2 (value related to 10 V or 20 mA).
-9999..+30000 [digit
1 p. 65
] (degrees if temperature), Default: 1000.
312
r.2. s . e .
Retransmission 2 State Error
Determines retransmission 2 value in case of error or anomaly.
If the retransmission output is 0-10V:
0 V
0 V. Default
10 v
10 V.
If the retransmission output is 0-20 mA or 4-20 mA:
0 ma
0 mA. Default
4 ma
4 mA.
20 ma
20 mA.
21.5 m a
21.5 mA.
313÷317 Reserved Parameters - Group U
Reserved parameters - Group U