36 - ATR244 - User manual
92 
mn.i.1
  Minimum Integral Time 1
Selects the min. integral time 1 value selectable by the automatic tune for the P.I.D. regulation 
of process 1.
0.0...1000.0 seconds. Default: 30.0 s.
93 
o . c . L.1
  Overshoot Control Level 1
The overshoot control function prevents this event during device switching on or when the 
setpoint is modified. 
Setting a too low value the overshoot may not be fully absorbed, while with high values the 
process could reach the setpoint more slowly.
Disab.
Lev. 1
Lev. 2
Lev. 3
Lev. 4
Lev. 5 (Default)
Lev. 6
Lev. 7
Lev. 8
Lev. 9
Lev. 10
94÷97  Reserved Parameters - Group E
Reserved parameters - Group E
GROUP F - 
reG.2
 - Autotuning and PID 2
98 
tun.2
  Tune 2
Selects autotuning type for command 2
diS a b.
  Disabled. If proportional band and integral time paramters are to selected to zero, the 
regulation is ON/OFF type. (Default)
Auto
  Automatic (Automatic P.I.D. parameters calculation )
M a n u.
  Manual (launch by keyboards or by digital input)
OncE
  Once (P.I.D. parameters calculation only at first start) 
SYncH.
  Synchronized (Autotuning managed by serial)
99 
s.d.t.2
  Setpoint Deviation Tune 2
Selects deviation from command setpoint 2 as threshold used by
autotuning to calculate P.I.D. parameters.
0-10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors). Default: 30.0.
100 
p. b. 2
  Proportional Band 2
Proportional band or process 2 P.I.D. regulation (Process inertia).
0 ON / OFF if t.i. equal to 0 (Default)
1...10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors).
101 
i . t. 2
  Integral Time 2
Integral time for process 2 P.I.D. regulation (process intertia duration).
0.0...2000.0 seconds (0.0 = integral disabled), Default 0.0
102 
d . t. 2
  Derivative Time 2
Derivative time for process 2 P.I.D. regulation (Normally ¼ of integral time).
0.0...1000.0 seconds (0.0 = derivative disabled), Default 0
103 
d . b . 2
  Dead Band 2
Dead band of process 2 P.I.D. 
0...10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors) (Default: 0)