38 - ATR244 - User manual
114
m.G.t.2
Max Gap Tune 2
Selects the max. process-setpoint gap beyond which the automatic tune recalculates PID
parameters of process 2.
0-10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors). Default: 2.0
115
m n .p.2
Minimum Proportional Band 2
Selects the min. proportional band value selectable by the automatic tune for the P.I.D. regulation
of process 2.
0-10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors). Default: 3.0
116
m a .p.2
Maximum Proportional Band 2
Selects the max. proportional band 2 value selectable by the automatic tune for the P.I.D.
regulation of process 2.
0-10000 [digit
1 p. 65
] (degrees.tenths for temp. sensors). Default: 80.0
117
mn.i.2
Minimum Integral Time 2
Selects the min. integral time 2 value selectable by the automatic tune for the P.I.D. regulation
of process 2.
0.0...1000.0 secondS. Default: 30.0 secondi.
118
o.c.L.2
Overshoot Control Level 2
The overshoot control function prevents this event during device switching on or when the
setpoint is modified.
Setting a too low value the overshoot may not be fully absorbed, while with high values the
process could reach the setpoint more slowly.
Disab.
Lev. 1
Lev. 2
Lev. 3
Lev. 4
Lev. 5 (Default)
Lev. 6
Lev. 7
Lev. 8
Lev. 9
Lev. 10
119÷122 Reserved Parameters - Group F
Reserved parameters - Group F