D. Installation - Ventilation
D.1.3.1 Temperature Set
Path: Home> Installation> Climate> Ventilation> Temperature set
The Temperature Settings of the Ventilation steps (marked with Step 1 relative set) refer to the set
Ventilation programmed in Settings>Climate (par. C.1): this Set can be set by Calendar (par. C.4).
For example with a Ventilation Set = 25.0° and a Step 1 relative set = 1.0° the start up temperature of
Step 1 will be of 26.0° (25.0° + 1.0°).
Apart the Step 1, the sets of start of the whole other Step (from Step 2 to Step 10) they are referred
to the start up temperature of the previous step.
Temperature set of Step 1 referred to the Ventilation set
programmed in Settings>Climate (par. C.1).
Temperature set of Step 2 referred to the start up temperature of
the previous step (Step 1).
Temperature set of Step 10 referred to the start up temperature of
the previous step (Step 9).
Ventilation differential: given a Ventilation step, it’s the difference
in temperature required to go back to the previous step.
Step 1 relative set
(Range: 0.0°...30.0°)
Step 2 relative set
(Range: 0.0°...1.0°...30.0°)
Continue until to..
Step10 relative set
(Range: 0.0°...1.0°...30.0°)
Ventilation different.
(Range: 0.0°...0.2°...30.0°)
Ventilation temperature probe
*1
Step 1
relative set
STEP
1
STEP
0
STEP
2
Continue until to..
STEP
10
Step 2
relative set
Step 10
relative set
Ventilation
Set referred to the Ventilation set programmed in Settings>Climate
This Set can be set by Calendar (see par. C.4 ).
*2
Ventilation steps are programmed “one by one” in sequence according to what was set in System
configuration (see par. D.C).
*1
The reference’s temperature of the Ventilation can be also the average among the probes of the
Ventilation, the Flaps probe, and the Heating probes (see Probe Average par. D.1.3.4).
The same for all
the other steps
(max 10)
OFF
*2
STEP 1
VENTIL.
Step 1 relative set
STEP 2
VENTIL.
OFF
*2
ON
*2
ON
*2
Step 2 relative set
Ventilation
Set referred to the Ventilation set programmed in Settings>Climate
This Set can be set by Calendar (see par. C.4)
Ventilation
different.
Ventilation
different.
Ventilation temperature probe