51
D. Installation - Ventilation
ppm CO2 set (over this value, ventilation rate is increased).
ppm CO2 intervention range.
Note: typical= 100ppm (1% of 10000 ppm).
Decrease of the temperature Ventilation set (see par. C.1) for each
CO2 intervention step higher than the Maximun CO2 value.
Make sure the Ventilation different. (par. D.1.3.1.F.3) is higher or
equal to this setting.
Maximum decrease of the Ventilation set for C02 intervention.
Maximun CO2
(Range: 0
pm
...2800
pm
...10000
pm
)
CO2 intervent. step
(Range: 0
pm
...50
pm
...1000
pm
)
Ventilation set decr.
(Range: 0.0°...30.0°)
Maximum set decr.
(Range: 0.0°...2.0°...30.0°)
D.1.3.6.4 Increase for C02/NH3
Path: Home> Installation> Climate> Ventilation> Conditionings> Increase for CO2/NH3
This function can increase ventilation rate (by reducing the Ventilation temperature set or by increasing
the % of Air changes) whenever CO2 or NH3 will be increasing some preset values.
ppm NH3 set (over this value, ventilation rate is increased).
ppm NH3 intervention range.
Note: typical= 1ppm (1% di 100 ppm).
Decrease of the temperature Ventilation set (see par. D.1) for each
NH3 intervention step higher than the Maximun NH3 value.
Make sure the Ventilation different. (par. D.1.3.1.F.3) is higher or
equal to this setting.
Maximum decrease of the Ventilation set for NH3 intervention.
Maximun NH3
(Range: 0.0
pm
...16.0
pm
...100.0
pm
)
NH3 intervent. step
(Range: 0.0
pm
...0.5
pm
...10.0
pm
)
Ventilation set decr.
(Range: 0.0°...30.0°)
Maximum set decr.
(Range: 0.0°...2.0°...30.0°)