68
D. Installation - Feeding
D.2.2 Distribution
Path: Home> Installation> Feeding> Distribution
Active only if the ‘Hopper max. level sensor’ is connected to Xfarm
(see Feeding config. par. D.C): defines the delay in activating the
hopper auger after the feed sensor start signal.
To avoid frequent on-off working of the silo auger due to the action
of the max level hopper sensor, this value has to be set according
to the time required by the feed hopper to become empty when
feeding lines are working.
In this way the hopper is being loading only when it’s really empty.
Feeders stop during silos loading? Yes-No.
Number of minutes the lights are turned off for during meal
distribution start.
Hopper sens. delay
(Range: 0
m
.00
s
...0
m
.05
s
...10
m
.00
s
)
Feeders stop load.
(Range: Yes...Si)
Light turn-off
(Range: 0
m
.00
s
...99
m
.00
s
)
D.2.3 Lighting
Path: Home> Installation> Feeding> Lighting
% of luminosity at light start up.
% of luminosity at light start up + time of Ramp up time.
Time ramp up duration.
Time ramp down duration.
Time during light permanence % at sunset.
Minimum luminosity
(Range: 0%...10%...100%)
Maximum luminosity
(Range: 0%...100%)
Ramp up time
(Range: 0
m
.00
s
...5
m
.00
s
...60
m
.00
s
)
Ramp down time
(Range: 0
m
.00
s
...15
m
.00
s
...60
m
.00
s
)
Minimum permanence
(Range: 0
m
.00
s
...60
m
.00
s
According to what was set in Configuration (see par. D.C) Xfarm can control lighting (by On / off output
and with dawn / sunset 0-10V output).
Operation lights
Light 0-10V
0%
100%
10%
50%
Ramp down
time
*2
Minimum
permanence
Light ON-OFF
OFF
ON
Realay
output
Minimum %
Maximum %
These timing can be programmed in
Settings> Feeding> Lighting cycle times
(par. C.2.2.)
TIME
Ramp up
time
*1
Stop hour
Light times
Start hour
Light times
*1
When lights period starts from 00:00 the ascent ramp is not activated.
*2
When lights period ends at 23:59 the descent ramp is not activated.