SD300
POWER ELECTRONICS
154
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen
Description
Default
value
Range
Function
Set on
RUN
Note: Comes from the previous page.
OPT.
DESCR.
FUNCTION
0
No
General deceleration
is carried out until a low
voltage trip occurs.
1
KEB1
When the input power
is lost, it charges the
DC link with
regenerated energy.
When the input power
is restored, so does
normal operation from
energy buffering
operation to the
frequency reference
operation. Operation
frequency acceleration
is set in Cn.83.
2
KEB2
When the input power
is lost, it charges the
DC link with
regenerated energy.
When the input power
is restored, it changes
from the energy
buffering operation to
the deceleration stop
operation. The
operation frequency
deceleration time is set
in dr.4.
Cn.78
[22]
Initial value for
KEB operation
125.0%
110.0 to
200.0%
Sets the start and stop points of the kinetic
energy buffering operation. The set values
must be based on the low voltage trip level
as 100% and the stop level (Cn.79) must be
higher than the start level (Cn.78).
NO
Cn.79
[22]
Value to stop
KEB operation
130.0%
Cn.78 to
210.0%
NO
[
22
] Displayed when Cn.77 is not set to 0 (NO).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Power Electronics SD300 Series and is the answer not in the manual?

Power Electronics SD300 Series Specifications

General IconGeneral
BrandPower Electronics
ModelSD300 Series
CategoryInverter
LanguageEnglish

Related product manuals