SD300
POWER ELECTRONICS
162
DESCRIPTION OF PROGRAMMING PARAMETERS
Screen
Description
Default
value
Range
Function
Set
on
RUN
In.65
Digital input 1
START
(+)
0 to 54
Digital Inputs configuration for individual use.
OPT.
DESCR.
FUNCTION
0
None
Not programmed entry.
1
START(+)
Send the start command
through an open contactor
(NO). The operation of the
Digital Input varies when
‘3 WIRE’ is selected.
2
START(-)
Send the reverse start
command through an
open contactor (NO). The
operation of the Digital
Input varies when 3
WIRE’ is selected.
3
RESET
Send a ‘Reset’ command
through digital inputs.
(NO)
4
EXTTRIP
Trigger an external fault to
stop the drive through
digital inputs (NO). Is
advisable to invert the
digital input logic
configured as Extreme
Fault and set it as contact
(NC). See parameter
In.87.
5
DISSTART
Stop the drive by
removing the motor output
power supply, forcing a
stop by inertia. (NO)
6
INCH1
Enable the speed
reference programmed in
dr.11. (NO)
Note: Continues on the next page