Installation and Operation Manual Page 41 of 104
(PVI-3.8/4.6-I-OUTD-US Rev.: 1.1)
WARNING: THE INPUT CURRENT SHALL NEVER EXCEED 14 Adc
(PVI-4.6-I-OUTD), 12.5 Adc (PVI-3.8-I-OTD) for each channel (single
contact in the terminal block “D.C. / ± IN1 e ± IN2").
WARNING: THE INPUT POWER FOR SINGLE CHANNEL SHALL
NEVER EXCEED 3 kW.
After the DC connection is completed, follow the instructions in section 3.3.7.
3.3.6.1 Independent Connection of the Aurora DC inputs
WARNING: Before performing any operation on the Switch Box power
input or on the Inverter, ALWAYS perform the disconnection procedure as
explained in section 3.3.1 or 3.3.2 of this manual.
User who wants to use each channel independently has to remove the parallel cables in
Fig. 16 and to connect DC wiring to each channel.
The switch “S1” indicated in Fig. 15 should be placed to position “IND” in order to
configure the inverter in independent mode.
Fig. 15 - Configuration switch