Installation and Operation Manual Page 99 of 104
(PVI-3.8/4.6-I-OUTD-US Rev.: 1.1)
8.2 Output values
Description
Value
PVI-3.8-I-OUTD
Value
PVI-4.6-I-OUTD
Rated output power 3,800 W 4,600 W
Max. continuous output
power
4,200W/ 3,800W/
3,300W
5000W/ 5000W/ 5000W
Grid voltage, maximum
range
183 to 304 Vac 183 to 304 Vac
Grid voltage, rated
277V single phase or
240V split phase or
208V single phase
(setting required)
277V single phase or
240V split phase or
208V single phase
(setting required)
Grid voltage, operating
range in compliance
with UL1741
regulations
88% to 110% of nominal
voltage
(211 to 264Vac for
V=240Vac)
88% to 110% of
nominal voltage
(211 to 264Vac for
V=240Vac)
Grid frequency,
maximum range
47 to 63 Hz 47 to 63 Hz
Grid frequency, rated 60 Hz 60 Hz
Grid frequency,
operating range in
compliance with
UL1741 regulations
59.3 to 60.5 Hz 59.3 to 60.5 Hz
Rated output current 13.7A/ 15.8A/ 16A 16.6A/ 19.1A/ 22.1A
Max. output current 16A/ 16A/ 16A 20A/ 20A/ 23A
Output overcurrent
protection
20A/ 20A/ 20A 25A/ 25A/ 30A