EasyManua.ls Logo

PowerFleet VAC4 - Page 70

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PowerFleet
®
VAC4 and VAC4S Hardware User’s Guide
085-00000700 Rev K
support@powerfleet.com
Page 73 of 103
13-Impact Sensor Er (Refer to Hardware Guide)
[FUNCTIONAL] System reports no impact sensor is installed.
Possible Cause(s)
Action
Impact sensor
connection
Verify that the impact sensor is properly connected to the VAC (connector C103).
Impact sensor cable
damage
Verify that the impact sensor cable is not damaged.
Replace sensor as needed and retest.
Impact sensor is not
getting power from
the VAC
Verify that the VAC is supplying adequate voltage by
unplugging the impact sensor connector and
connecting a voltmeter to pin 1 (positive) and pin 8
(negative) on C103 of the VAC. The image at right
shows how to read the pin layout and direction.
You must have 5.5 ± 0.5 volts DC.
If the VAC is not supplying 5.5 ± 0.5 VDC
o Complete an RMA Request form (See Appendix A)
o Call PowerFleet’s Customer Service for an RMA number.
o Only the VAC should be returned for analysis/repair.
o Once VAC is removed, the system MUST be hard-bypassed to use vehicle.
Follow instructions on how to hard-bypass the system (See Appendix B).
Faulty impact sensor
Complete an RMA Request form (See Appendix A)
Call PowerFleet’s Customer Service for an RMA number.
Only the Impact sensor should be returned for analysis/repair.
14-SPI Error Low (Refer to Hardware Guide)
[FUNCTIONAL] The VAC cable is picking up electrical noise causing SPI errors greater than 1% of the time.
Possible Cause(s)
Action
VAC Cable
Visually inspect the VAC cable to verify that the VAC cable is not damaged.
Replace the cable as needed.
Electrical noise
Verify that the VAC cable is routed away from high electrical noise devices such as
traction motors and contactors.
If chassis noise is present, reroute the cable and retest.
15- Run Configuration Wizard [SHUTDOWN] The configuration wizard was never run for the VAC that is currently
installed on the vehicle.
Possible Cause(s)
Action
VAC configuration
Log in to the VAC as a Maintenance operator and re-run the configuration wizard
(see Section 2)

Table of Contents

Related product manuals