EasyManuals Logo

Powtran PI9000 series User Manual

Powtran PI9000 series
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
Chapter 5 Function parameter
140
inverter multi-functional DO will output "AI1 input overrun"signal, so as to indicate whether
the AI1 input voltage is within the set range or not.
F7.52 to
F7.53
Reserve
F7.54
Jog mode setting
3
Bits
Jog direction
002
Forward
0
reverse
1
Determine the
direction from the
main termina
2
Ten
bits
End running
state by
Jogging
Restore to the
state before
jogging
0
stop running
1
Hun
dred
bits
Acceleration/
de
celeration time
after stop
jogging
Recover to the
acceleration/
decel
eration time
before jogging
0
Keep the
acceleration/
decel
eration time when
jogging
1
Note: Superscripts
3
software version for C3.00 above with MCU keyboard have this
function.
5-2-10.Fault and protection:F8.00-F8.35
Code
Parameter
name
Setting range
Factory
setting
Chang
e limits
F8.00
Overcurrent
stall gain
0 to 100
20
F8.01
Overcurrent
stall
protection
current
100% to 200%
150%
In the process of the inverter acceleration, when the output current exceeds the
overcurrent stall protection current, the inverter stops ac/deceleration process and remains