Chapter 5 Function parameter
177
0:not displays
1:displays
y0.04
Function code
modification
properties
Modifiable
0
0
Not modifiable
1
User can set whether function code parameter can be modified or not, so as to prevent
the risk that function parameters are altered unexpectedly.
If the function code is set to 0, all function code can be modified; while it is set to 1, all
function code can only be viewed, can not be modified.
5-2-21.Fault query:y1.00-y1.30
Code
Parameter
name
Setting range
Factory
setting
Change
limits
y1.00
Type of
the first
fault
0 to 51
-
y1.01
Type of
the second
fault
0 to 51
-
y1.02
Type of
the third(at
last) fault
0 to 51
-
Record the type of the last three faults of inverter, 0 for no fault. Please refer to the
related instructions for the possible causes and solutions for each fault code.
Failure type table:
No.
Failure type
0
No fault
1
Inverter unit protection
2
Acceleration overcurrent
3
Deceleration overcurrent
4
Constant speed
overcurrent
5
Acceleration
overvoltage
6
Deceleration
overvoltage
7
Constant speed
overvoltage
8
Control power failure
9
Undervoltage
10
Inverter overload
11
Motor Overload
12
Input phase loss