EasyManuals Logo

Powtran PI9000 series User Manual

Powtran PI9000 series
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
Chapter 5 Function parameter
71
No.
Code
Parameter name
Setting range
Factory
setting
Change
Reference
page
382.
E1.49
15 stage ac/deceleration
time selection
0 to 3
0
160
383.
E1.50
Simple PLC run-time
unit
0: S (seconds)
1: H (hours)
0
160
384.
E1.51
Multi-stage command
0 setting mode
0: Function code
E1.00 reference
1:
Analog AI1
reference
2:
Analog AI2
reference
3:
Panel
potentiometer
setting
4:
High-speed
pulse
setting
5:
PID control
setting
6:
Keyboard set
frequency
(F0.01)
setting
,
UP/DOWN can
be modified
0
160
5-1-17.E2 Group - PID function
No.
Code
Parameter name
Setting range
Factory
setting
Change
Reference
page
385.
E2.00
PI
D setting source
0: E2.01 setting
1: Analog AI1
reference
2: Analog AI2
reference
3: Panel
potentiometer setting
4: High-speed pulse
setting
5: Communications
reference
6: Multi-stage
command reference
0
161
386.
E2.01
PID keyboard setting
0.0% to 100.0%
50.0%
161