EasyManuals Logo

Powtran PI9000 series User Manual

Powtran PI9000 series
256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #166 background imageLoading...
Page #166 background image
Chapter 5 Function parameter
160
E1.44
13 stage running time T13
0.0s(h) to 6500.0s(h)
0.0s(h)
E1.45
13 stage ac/deceleration time
selection
0 to 3
0
E1.46
14 stage running time T14
0.0s(h) to 6500.0s(h)
0.0s(h)
E1.47
14 stage ac/deceleration time
selection
0 to 3
0
E1.48
15 stage running time T15
0.0s(h) to 6500.0s(h)
0.0s(h)
E1.49
15 stage ac/deceleration time
selection
0 to 3
0
Multi-speed operation and deceleration time selection 0 to 3 , corresponding to the function
code:
0: F0.13F0.14
1:F7.08F7.09
2:F7.10F7.11
3:F7.12F7.13
E1.50
Simple PLC run-time unit
S (seconds)
0
0
H (hours)
1
E1.51
Multi-stage command 0
reference manner
Function code
E1.00 reference
0
0
Analog AI1
reference
1
Analog AI2
reference
2
Panel
potentiometer
reference
3
High-speed pulse
reference
4
PID control
reference
5
Keyboard set
frequency
(F0.01)
reference,
UP/DOWN can
be modified
6
This parameter determines the multi-stage command 0 reference channel.
The multi-stage command 0 not only can select E1.00, but also there are a variety of
other options so as to facilitate switching between the multi-stage command and the other
reference manner.
5-2-17.PID function: E2.00-E2.27
PID control is a commonly used method of process control, a closed loop system is
formed by the proportional, integral and differential operation of difference between the
controlled value feedback signal and target value signal and by adjusting the inverter

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Powtran PI9000 series and is the answer not in the manual?

Powtran PI9000 series Specifications

General IconGeneral
BrandPowtran
ModelPI9000 series
CategoryInverter
LanguageEnglish

Related product manuals