Chapter 5 Function parameter
73
No.
Code
Parameter name
Setting range
Factory
setting
Change
Reference
page
404.
E2.19
PID parameter
switching conditions
0:
no switching
1:
switching via
terminals
2:
automatically
switching according
to deviation.
0
163
405.
E2.20
PID parameter
switching deviation 1
0.0% to E2.21
20.0%
163
406.
E2.21
PID parameter
switching deviation 2
E2.20 to 100.0%
80.0%
163
407.
E2.22
PID integral
properties
Units digit: integral
separation
0: Invalid
1: Valid
Tens digit: whether
stop integration when
output reaches limit
0: continue
1: stop
00
164
408.
E2.23
PI
D initial value
0.0% to 100.0%
0.0%
164
409.
E2.24
PID initial value hold
time
0.00s to 360.00s
0.00s
165
410.
E2.25
Maximum deviation
of twice
outputs(forward)
0.00% to 100.00%
1.00%
165
411.
E2.26
Maximum deviation
of twice
outputs(backward)
0.00% to 100.00%
1.00%
165
412.
E2.27
Computing status
after PID stop
0:
stop without
computing
1: stop with
computing
1
165
5-1-18.E3 Group Virtual DIVirtual DO