Chapter 5 Function parameter
40
No.
Code
Parameter
name
Setting range
Factory
setting
Cha
nge
Referen
ce page
53.
F0.11
Command
source selection
0.Keyboard control (LED off)
1.Terminal block control (LED
on)
2.Communications command
control (LED flashes)
3.
Keyboard control+
Communications command
control
4. Keyboard control+
Communications command
control+ Terminal block
control
0
93
54.
F0.12
Binding
frequency
source for
command
source
Units digit: binding frequency
source selection for operation
panel command
Tens digit: terminal command
binding frequency source
selection (0 to 9, same as units
digit)
Hundreds digit:
communication command
binding frequency source
selection (0 to 9, same as units
digit)
000
94
55.
F0.13
Acceleration
time 1
0.00s to 6500s
Depend
s on
models
95
56.
F0.14
Deceleration
time 1
0.00s to 6500s
Depend
s on
models
95
57.
F0.15
Ac/Deceleratio
n time unit
0:1 second
1:0.1 second
2:0.01 second
1
95
58.
F0.16
Ac/deceleration
time reference
frequency
0: F0.19(maximum frequency)
1: Set frequency
2: 100Hz
0
95
59.
F0.17
Carrier
frequency
adjustment as
per temperature
0:
NO
1:
YES
0
95

Table of Contents