Chapter 5 Function parameter
48
No.
Code
Parameter name
Setting range
Factory
setting
Change
Reference
page
speed
2: start from
maximum frequency
3:
Rotate speed
tracking method
3
139.
F3.02
Speed tracking
value
1 to 100
20
117
140.
F3.03
Start frequency
0.00Hz to 10.00Hz
0
.
00Hz
117
141.
F3.04
Hold time for start
frequency
0.0s to 100.0s
0
.
0s
117
142.
F3.05
Start DC braking
current
0% to 100%
0%
118
143.
F3.06
Start DC braking
time
0.0s to 100.0s
0
.
0s
118
144.
F3.07
Stop mode
0: Deceleration
parking
1: Free stop
0
118
145.
F3.08
Initial frequency of
stop DC braking
0.00Hz to F0.19
(maximum
frequency)
0
.
00Hz
118
146.
F3.09
Waiting time of stop
DC braking
0.0s to 100.0s
0
.
0s
118
147.
F3.10
Stop DC braking
current
0% to 100%
0%
118
148.
F3.11
Stop DC braking
time
0.0s to 100.0s
0
.
0s
118
149.
F3.12
Braking utilization
rate
0% to 100%
100%
119
150.
F3.13
Ac/deceleration
mode
0: Linear acceleration
and deceleration
1: S curve
acceleration and
0
119

Table of Contents