EasyManuals Logo

ProSoft Technology PLX3x Series User Manual

ProSoft Technology PLX3x Series
215 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
EIP Protocol PLX3x Series Multi-Protocol Gateways
User Manual
Page 54 of 215 ProSoft Technology, Inc.
January 25, 2018
MSG Instruction Type - CIP
The following table defines the relationship of the user data area in the gateway’s
internal database to the addresses required in the MSG CIP instructions:
Data-
base
Address
CIP
Integer
CIP Boolean
CIP Bit Array
CIP Byte
CIP DINT
CIP Real
0
Int_data
[0]
BoolData[0]
BitAData[0]
SIntData[0]
DIntData[0]
RealData
[0]
999
Int_data
[999]
BoolData[15984]
SIntData[1998]
1000
Int_data
[1000]
BoolData[16000]
BitAData[500]
SIntData[2000]
DIntData[500]
RealData
[500]
1999
Int_data
[1999]
BoolData[31984]
SIntData[3998]
2000
Int_data
[2000]
BoolData[32000]
BitAData[1000]
SIntData[4000]
DIntData[1000]
RealData
[1000]
2999
Int_data
[2999]
BoolData[47984]
SIntData[5998]
3000
Int_data
[3000]
BoolData[48000]
BitAData[1500]
SIntData[6000]
DIntData[1500]
RealData
[1500]
3999
Int_data
[3999]
BoolData[63999]
SIntData[9998]
MSG Instruction Type - PCCC
The following table defines the relationship of the user data area in the gateway’s
internal database to the addresses required in the MSG PCCC instructions:
Database Address
File size 100
Database Address
File size 100
0
N10:0
0
N10:0
999
N19:99
999
N19:99
1000
N20:0
1000
N20:0
1999
N29:99
1999
N29:99
2000
N30:0
2000
N30:0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ProSoft Technology PLX3x Series and is the answer not in the manual?

ProSoft Technology PLX3x Series Specifications

General IconGeneral
BrandProSoft Technology
ModelPLX3x Series
CategoryGateway
LanguageEnglish

Related product manuals